ZXQJ electric actuator controller

Technical Parameters
●Power supply voltage: AC380VAC
● Rated power: 0.8KW
● Control accuracy: 0.1% ~ 3.0% (adjustable through U4 parameter)
● It can be connected to electric actuator feedback signal: potentiometer 500Ω-10KΩ
● It can receive external control signal (DC): 4-20mA, switching value.
● Input impedance (4-20mA): 250Ω;
● It can be set by modifying U1 parameters:
①DRTA/forward action, RVSA/reverse action mode
②When the input signal is interrupted: "Interrupt" mode-OPEN (open), STOP (stop), SHUT (closed)
● Output actuator position signal: low drift output 4-20mA, corresponding to the actuator from fully closed to fully open, the signal is completely Isolated from input (photoelectric isolation), output load ≤500Ω
●Ambient temperature: 0-70℃
● Over-temperature protection function (can be set): When the temperature inside the positioner shell is ≥70°C, the actuator control will stop
● The action range of the actuator corresponding to the input signal can be freely calibrated through the buttons (generally calibrated to the fully closed and fully open positions of the electric actuator)
● The maximum valve position limit value and the minimum valve position limit value can be set
● Password lock to prevent misoperation
● Anti-actuator frequent startup function
●With fault alarm code indication function (E-0X)
● Intelligent step adjustment and precise positioning based on input signal and actuator corner position
Operation panel

Product display



Preparation before debugging
Since the calibration of the "zero point" and "full scale" of the controller must be carried out within the linear working range of the position sensing potentiometer, calibration within the "dead zone" of the potentiometer will cause serious consequences such as program confusion. Therefore, the following preparations must be carried out before calibration.
1. Verification of the direction of the position signal: Press the A/M key to switch to the manual state and perform a trial run; observe whether the opening change trend of the digital display (the number decreases when it is closed and the number increases when it is open) conforms to the defined direction. If they are not consistent, replace the two points of potentiometer 1 and 3 and adjust the wiring.
2. Check the wiring with the actuator: the closed dry contact and the open dry contact are normally closed contacts (that is, after the contact is switched from normally closed to normally open, it is judged that the actuator is closed or opened). If the actuator does not have an overheat protection contact output (normally closed point), please short-circuit the overheat protection contact input on the module.
Analysis and diagnosis of common faults

Hot Tags: zxqj actuator controller integral electronic module, China, manufacturers, suppliers, factory, buy, price, quotation, Flange Gate Valve, Explosion Proof Butterfly Valve Actuator, Electric Quarter Turn Actuator, Linear Electric Actuator For Rotork, Motorized Butterfly Valve, Electric Water Gate Valve