Trouble phenomenon: After powering on the electric actuator, it is found that the power indicator does not light up, the servo amplifier board has no feedback, and the signal does not act.
Failure judgment and maintenance process:
Because the power indicator is not on, first check whether the fuse is open. After checking that the fuse is intact and a comprehensive failure phenomenon, it can be inferred that the fault may occur in the power supply part of the servo board. Then check the power indicator, and use a multimeter to detect the indicator. Open circuit, replace the indicator and troubleshoot.
Conclusion: An open circuit of the power indicator will cause the entire servo board to not work.
2. Failure phenomenon: (found during debugging)
After the actuator of the electric actuator is energized, the signal can be turned on, but it will not work when it is off.
Fault judgment and maintenance process: first check the feedback circuit carefully and confirm that the feedback signal is not faulty. The on indicator light is on when the on signal is given, indicating that the on is normal, and the off indicator is not on when the off signal is given, indicating that there is a problem with the thyristor off. Check the off indicator, use a multimeter to detect that the off indicator is open, replace it and eliminate the fault.
Conclusion: The thyristor does not work when the off and on indicator lights are off (open circuit).